MCQ Practice Test — Category 10
Star Delta & Motor Starters MCQ
DOL, Star-Delta, Auto Transformer, VFD — Gulf me motor starting methods ka poora knowledge. Har supervisor ko ye aana chahiye.
10 Questions (Page 1)
Easy-Hard Level
Hinglish Explanation
Attempted: 0/10
Correct: 0
Wrong: 0
Question 01Easy
Star-Delta starter me motor pehle Star me kyon start hota hai?
AZyada torque ke liye
BSpeed badhane ke liye
CStarting current kam karne ke liye — Star me voltage 1/√3 milta hai
DCooling ke liye
✓ Sahi Jawab: C
Star connection me motor ke har winding ko 415/√3 = 240V milta hai instead of full 415V. Isse starting current 1/3 ho jaata hai. Koi bhi motor full voltage pe directly start hone pe 6-8 times FLC current draw karta hai — ye supply ko disturb karta hai. Star-Delta ye problem solve karta hai.
Question 02Easy
Star-Delta starter me kitne contactors hote hain?
A1 contactor
B3 contactors (Main, Star, Delta)
C5 contactors
D2 contactors
✓ Sahi Jawab: B — 3 Contactors
Star-Delta starter me 3 contactors: (1) Main contactor — hamesha ON, supply deta hai. (2) Star contactor — starting pe ON, motor windings star me connect karta hai. (3) Delta contactor — timer ke baad ON, full voltage. Star aur Delta contactor ek saath ON nahi ho sakte — interlock zaroori hai.
Question 03Medium
Star-Delta transition ke time kya problem aati hai?
ACurrent/Torque transient spike aata hai — open transition problem
BMotor stop ho jaata hai
CKoi problem nahi hoti
DVoltage zyada ho jaati hai
✓ Sahi Jawab: A
Open transition problem: Star contactor OFF hone aur Delta contactor ON hone ke beech brief moment me motor supply se disconnect hota hai. Is moment pe current transient spike aata hai. Closed transition Star-Delta (with transition resistors) ya VFD se ye problem avoid hoti hai. Gulf me bade motors pe closed transition preferred hai.
Question 04Medium
Gulf me KAHRAMAA rule ke mutabik kaunse motors ke liye DOL allowed nahi hai?
A1kW se upar
B3kW se upar
C7.5kW se upar
D5.5kW se upar
✓ Sahi Jawab: D — 5.5kW se upar
KAHRAMAA Qatar rule: 5.5kW (7.5HP) se upar motors ke liye DOL nahi — Star-Delta ya Soft Starter ya VFD mandatory. Isse supply voltage dip avoid hoti hai. Qatar University, Sidra Hospital ke HVAC motors sab Star-Delta ya VFD se start hote hain. India me ye rule strict nahi hai lekin Gulf me pakka follow karo.
Question 05Medium
Star-Delta timer kitne seconds pe set karte hain?
A1 second
B5-15 seconds (motor type pe depend)
C60 seconds
DKoi timer nahi hota
✓ Sahi Jawab: B — 5-15 seconds
Star-Delta timer 5-15 seconds typically. Motor ki inertia aur load pe depend karta hai. Light load = 5-7 sec. Heavy load (pump, compressor) = 10-15 sec. Timer bahut kam set karne pe motor Star me hi Delta switch ho jayega aur current spike zyada hogi. Motor current monitor karo — jab Star me current stable ho jaaye tabhi switch karo.
Question 06Medium
Soft Starter ka Star-Delta pe kya advantage hai?
ASasta hota hai
B3 contactors ki zaroorat nahi
CSmooth acceleration, no current spike, no torque jerk — adjustable ramp up
DSpeed control deta hai
✓ Sahi Jawab: C
Soft Starter thyristors se voltage gradually badhata hai — smooth acceleration, zero current spike, zero torque jerk. Star-Delta me transition spike hoti hai — Soft Starter me nahi. Ramp-up time adjustable (2-30 sec). Conveyor, pump, compressor ke liye ideal. Disadvantage: speed control nahi — sirf starting ke liye. VFD full speed control bhi deta hai.
Question 07Hard
Star-Delta starter ke liye motor ki winding kaunsi honi chahiye?
ADelta rated — motor nameplate pe Delta connection voltage supply voltage ke barabar ho
BStar rated
CKoi bhi motor chalega
DSingle phase motor
✓ Sahi Jawab: A
Star-Delta ke liye motor Delta rated hona chahiye. 415V supply pe motor nameplate pe Δ/Y = 415V/240V hona chahiye. Delta pe 415V — isi liye Star me 240V milta hai (reduced). Agar motor Star rated (415V) hai to Star-Delta lagane pe Star me 240V milega — motor undervolted start hoga. Gulf interview me ye tricky sawaal hai.
Question 08Hard
Star-Delta me interlock kyun zaroori hai?
ACost save karne ke liye
BStar aur Delta contactors ek saath ON na hon — short circuit prevent karne ke liye
CMotor speed control ke liye
DDecoration ke liye
✓ Sahi Jawab: B
Star aur Delta contactors ek saath ON hone pe 3-phase short circuit hoga — explosive failure. Mechanical interlock (physical locking) + Electrical interlock (NC contact in coil circuit) dono lagao. Ye fundamental safety requirement hai. Gulf me Star-Delta panel wiring me ye double interlock mandatory check hai.
Question 09Hard
22kW motor ke liye Star-Delta starting current approximately kitna hoga? (FLC = 42A, DOL starting = 6x)
A252A (6x FLC)
B42A (FLC only)
C126A (3x FLC)
D84A (2x FLC, i.e., 1/3 of DOL starting)
✓ Sahi Jawab: D — 84A
DOL starting = 6 × 42 = 252A. Star-Delta = 252/3 = 84A. Ye 2x FLC hai — bahut better than DOL. Gulf me 22kW pump motor Star-Delta pe start hone pe 84A peak current — transformer pe load kam rehta hai. Motor Starting Current Calculator se verify karo.
Question 10Hard
Kab Star-Delta ki jagah VFD lagana better hai?
AKoi farak nahi
BHamesha VFD better hai
CJab variable speed control chahiye ya energy saving critical ho — pumps, fans, HVAC
DJab motor purana ho
✓ Sahi Jawab: C
VFD better hai jab: Variable speed chahiye (pump flow control, fan speed), energy saving critical (50% speed = 87% energy saving — cube law), frequent start/stop (VFD motor ko protect karta hai). Star-Delta better hai: fixed speed applications, simple control, lower cost. Sidra Hospital HVAC me VFDs lage hain — energy saving huge hai.
VoltGuru.in — Star Delta & Motor Starters MCQ — Free for Gulf Electricians