Voltage Drop
Calculator
3-Phase aur Single Phase — Copper aur Aluminium cable. IEC standard ke hisaab se Pass/Fail result. Gulf sites ke liye must-have tool.
Saari values daalo — drop volts mein, percentage mein, aur Pass/Fail IEC standard ke saath milega.
Voltage Drop — Kya Hota Hai?
Bhai, Gulf ki har badi site pe — Qatar University ho, Sidra Hospital ho ya koi industrial plant — ek common problem hai: cable itni lambi hai ki load tak pahunchte pahunchte voltage gir jaata hai. Isko hi Voltage Drop kehte hain.
Main Mohammad Arif hoon, 12+ saal ka experience hai. Maine dekha hai Qatar University site pe 200 meter ki cable pe motor chalna band ho gayi — kyunki voltage drop 8% se zyada tha aur motor ko enough voltage nahi mil rahi thi. Agar yeh calculator tab hota, 2 ghante ki investigation 2 minute mein hoti.
Formula — 3-Phase aur Single Phase
1-Phase: VD = 2 × I × R × L / 1000
R = resistivity / cross-section (mΩ/m)
VD% = (VD / V_supply) × 100
IEC 60364 Limits — Gulf Standard
KAHRAMAA Qatar aur DEWA UAE dono IEC 60364 follow karte hain. Yeh limits mandatory hain:
| Load Type | Max Drop | Gulf Sites |
|---|---|---|
| Lighting | 3% | Emergency lights, office lighting |
| Power / Motor | 5% | AC units, pumps, motors |
| Sub-distribution | 8% | Distribution boards to sub-DBs |
Resistivity Values (at 70°C)
| Material | Resistivity | Use |
|---|---|---|
| Copper | 0.0183 Ωmm²/m | Standard Gulf wiring |
| Aluminium | 0.0296 Ωmm²/m | Large feeders, overhead |
Problem: 50A motor, 415V 3-phase, 120m cable, 25mm² Copper
R = 0.0183 / 25 = 0.000732 Ω/m
VD = 1.732 × 50 × 0.000732 × 120 = 7.61V
VD% = 7.61 / 415 × 100 = 1.83% → PASS ✓ (limit 5%)
Receiving Voltage = 415 – 7.61 = 407.4V — Motor ke liye safe